Petroleum Terminal Handling and Diesel Exhaust Fluid

OEL8000IIP-W OMNTEC Manufacturing, Inc. 1993 Pond Road Ronkonkoma, NY 11779 USA TEL: (631) 981-2001 FAX: (631) 981-2007 Email: [email protected] UPSTREAM: www.innovative-sensor.com DOWNSTREAM: www.omntec.com SPECIFICATIONS Required wireless interface DataCheck™Serial Receiver part no. DC-RX-SR-X Input power 100-240 VAC, ± 10%, 50W Weight 20 lb. ( 9 kg) Approvals UL-listed, CUL-listed, CE-listed, CCOE AUDIO-VISUAL FEATURES Display 4 line by 40 character backlit LCD Printer 36- character thermal Audible alarm 85 dB piezoelectric horn Keypad 20- key oil-resistant tactile Status indicators 3 LEDs (OK, Fault, Alarm) OEL8000II OPTIONAL ACCESSORIES IB-NET Ethernet TCP/IP interface board Can be configured to automatically send alarms and reports via e-mail MDR-2 14,400 baud fax/modem module Can be configured to automatically FAX alarms and reports IB-RAS Remote annunciator interface board RAS-series Various remote annunciator systems IB-RB-2 Output relay board (4 SPDT relays per board, each rated 120 VAC @ 5A) IB-12V Low-voltage interface board IB-C420 Analog output board (4-20 mA) BX series sensors Various electronic and optoelectronic sensors used for leak detection, temperature, pressure, etc. BX Universal Translators available for custom applications. BX series are RS485 multidrop, and are intrinsically safe when properly wired to OEL8000IIP-W