NEE Propane & Natural Gas Equipment Catalogue

CANADA’S LEADER IN ENERGY PRODUCTS EQUIPMENT PLANT, TRUCK & TANK EQUIPMENT EXCESS FLOW VALVES Squibb Taylor Excess Flow Valves Intended to prevent large discharges of LPG vapour or liquid to the atmosphere due to a break in the hose or piping system. WARNING! A break or leak downstream of an excess flow valve that does not allow a flow equal to the valve flow rating will not actuate the valve and could cause a hazardous condition. For this reason, system operators should be familiar with the shutoff valves in the system so that necessary precautions can be taken in an emergency. NEE # Application and Style Inlet Connection Outlet Connection Closing Flow Rate Closing Flow Differential Pressure * A1714-225 Tanks Style A 3” M NPT 2” F NPT 225 GPM 6 PSIG A1706-50 Tanks or In-Line Style B 1 1/4” M NPT 1 1/4” M NPT 50 GPM A1708-95 2” M NPT 95 GPM 14 PSIG A1715-165 3” M NPT 2” M NPT 165 GPM 5 PSIG A1711-95 Tanks or In-LineStyle C 2” M NPT 2” M NPT and 1 1/4” F NPT 95 GPM 6.5 PSIG A1713-165 3” M NPT and 2” F NPT 165 GPM 6 PSIG A1713 225 GPM * @ 100 PSIG inlet; discharging to atmosphere. ~~~ Care must be taken to be sure the valve’s closing rate is less than the capacity of the LPG system in which the valve is installed! Excess Flow Manifold Adapter Allows for manifolding of ASME & DOT cylinders while providing excess flow protection for container vapour outlet valves. NEE # Description Closing Flow (US GPM) ME353EX9 M POL x 3/8” Male Flare 0.9 ME353EX18 1.8 ME354EX9 M POL x 1/2” Male NPT 0.9 ME354EX18 1.8 NEE # Description Closing Flow (US GPM) ME355EX9 M POL x 1/2” Male Flare 0.9 ME355EX18 1.8 ME356EX9 M POL x 5/8” Male Flare 0.9 ME356EX18 1.8 Style A Style C Style B ME353EX

RkJQdWJsaXNoZXIy NDE1MjE4