EATON Aerospace Group TF100-80E May 2013 3 Installation Information It is critical that the mating coupler (shown at right) be connected correctly and the pit lid be able to close completely. The hydrant valve’s installation depth depends upon the brand of pit used. The thickness of the pit lid should be checked to be sure that it will clear the hydrant valve before setting the pit. The dimensions noted herein were correct for pits made in the United States at the time of printing. Eaton cannot be responsible for changes in the pits. The dimensions, shown are for reference only. Technical Information • Working Pressure — 300 psi (20.7 bar) • Closing Time — 2 to 5 seconds • Overshoot — 60.0 gals (225 liters) maximum at 1200 US gpm (4500 l/min.) • Pilot valve air pressure required for Options E, F, J, U or X — 60 psi min. (4.2 bar) • Mates Eaton’s Carter Hydrant Coupler Models 60600, 60600-1, 60700-1, 64702, 64800, 64801, 64802, 64804, 64900, 64901, 64902, 61525 and all other API style couplers Dimensional Specifications The drawing (right) provides envelope dimensions for installation purposes only. They are not intended for inspection purposes. Technical Data Dimensions are shown in inches (millimeters)