15 O-81588 and SO-415VX5 Separator Reduces free and emulsified water to less than 50 ppm in diesel, and less than 15 ppm in jet fuel/avgas. Used in place of Aquacon® cartridges for continuous removal of free water For use in the Parker Velcon Vel-Max® housings DESCRIPTION The Parker Velcon coalescer and separator are installed together in the Vel-Max® housing to remove water and dirt from fuel. The fuel passes from the outside to the inside through the coalescer. Dirt is filtered out of the fuel and free/ emulsified water in fuel is coalesced. The coalesced water droplets, which form on the inside of the coalescer, are repelled from going further down-stream by the separator. The water settles down to the sump where it is manually drained. Replacement Cartridges for Vel-Max® Housings O Series Coalescer and SO Separator Remove Water and Dirt from Diesel, Jet Fuel and Avgas SPECIFICATIONS Maximum Operating Temperature is 160°F / 71°C Flow direction: outside to inside pH range: 5 to 9 Coalescer Changeout at 15 psid MAXIMUM RECOMMENDED FLOW RATES Housing with Cartridges Jet Avgas Diesel gpm lpm gpm lpm gpm lpm VX-1 37 140 55 208 25 95 VX-2 75 284 100 378 50 189 VX-3 112 424 168 636 75 284 For more information on the Vel-Max® Filter Vessel please refer to data sheet #1961. Vel-Max® and Aquacon® are registered trademarks of Parker Hannifin. OUTLET DRAIN LO DP SIGHT GLASS WATER PROBE CONNECTION ON BACK VENT SEPARATOR COALESCER INLET HI DP RELIEF VALVE VELMAX® FILTER/SEPARATOR CONFIGURATION