Veeder-Root Sensor Application Guide 14 MicroSensor The small, easy to install solid-state MicroSensor is designed detect liquid in the interstitial space of a steel tank or a fill riser containment. Sensor Detection Capabilities - Alarm Conditions • The presence of any liquid in the sensing location triggers a Fuel Alarm. • An open sensor triggers a Sensor Out Alarm. Operating Capabilities • Operating temperature range: -32 to +60°C. • Storage temperature range: -40 to +70°C. • Cable length: 25 feet • Sensor dimensions: 0.8” high, 0.4” high, 2.2” long. Compatible Consoles TLS-450, TLS-350Plus, PC-350Plus, TLS-350R, PC-350R Sensor Interface Module TLS-350 series - Type A Sensor interface module (P/N 329956-001) accepts up to 8 sensors (a maximum of 64 sensors could be monitored by a console). TLS-450 - USM (P/N 332812-001) accepts up to 16 sensors Console Software Compatibility • TLS-350 series (Version 2 or later) • TLS-450 (All) Compatible Fuels • Unleaded gasoline • Unleaded with up to 5% methanol, 85% ethanol, or 15% MTBE • Leaded gasoline • Diesel • Kerosene • Jet fuel • Aviation gasoline Sensor/Cable Length Configuration MicroSensor with 25-foot cable - Form Number 794380-344. Accessories Riser cap and adaptor kit (2”) - P/N 312020-928 Related Sales Literature Visit our website at www.veeder.com for more information on Veeder-Root products and services. Weatherproof junction box Seal-off 1/2'' rigid conduit (to console) 14'' min. dia. manhole 1'' conduit Riser MicroSensor Riser containment Tank 1/2'' rigid conduit sensors\mrsenap.eps Minimum riser diameter 1 inch Cord grip Weatherproof junction box 14'' min. dia. manhole Seal-off sensors\missenap.eps 1/2-inch rigid conduit (to Console) Sensor must rest on bottom of tank Sensor cable 1/2'' to X'' reducer (x = riser diameter) Steel tank Fig. 10 Typical Interstitial MicroSensor Installation - Steel UST Fig. 11 Typ. MicroSensor Installation in Riser Containment
RkJQdWJsaXNoZXIy NDE1MjE4